Description
Daikin VRV Air-Cooled Heat Pump
Daikin VRV Air-Cooled Heat Pump RXYSQ6TY9 - VRV IV S series
Elevate your climate control with the Daikin VRV Air-Cooled Heat Pump, designed to offer superior efficiency, flexibility, and comfort for any building.
Key Features
- Wide Range of Indoor Units: Compatible with both VRV systems and stylish indoor units such as Daikin Emura and Nexura, providing a versatile solution for any aesthetic or functional need.
- Advanced VRV IV Technology: Incorporates Variable Refrigerant Temperature (VRT) and full inverter compressors to enhance energy efficiency and system performance.
- Peak Consumption Control: Allows for limiting peak power consumption between 30% and 80%, ideal for managing high power demand periods.
- Weather-Dependent VRT: Tailor your VRV system for optimal seasonal efficiency and comfort using intelligent, weather-responsive VRT.
- i-NET Monitoring Service: Ensure your system remains in top condition with continuous monitoring, defect prediction, and clear insights into operating conditions and usage for maximum efficiency and longevity.
- Comprehensive Thermal Solutions: Address all thermal needs, including precise temperature control, ventilation, air handling, and Biddle air curtains, through a single point of contact.
- VRV Control Systems Compatibility: Seamlessly connect to all VRV control systems for integrated management.
- Space-Saving Design: Compact and flexible installation options make it suitable for various spaces, minimizing visual impact.
- 3-Stage Night Mode: Reduce noise levels at night with a 3-stage night mode, ensuring a quieter environment.
- Environmental Responsibility: Support refrigerant reuse with Daikin’s LOOP technology, contributing to a sustainable future.
Inverter Technology
- Inverter Compressors: Continuously adjust compressor speed to actual demand, resulting in fewer power-consuming starts and stops, decreased energy consumption (up to 30%), and more stable temperatures.
Variable Refrigerant Temperature
- Intelligent System: Ensures the highest energy savings with additional comfort, adapting to better suit application requirements.
Upgrade to the Daikin VRV Air-Cooled Heat Pump and experience the perfect blend of efficiency, flexibility, and advanced technology for your heating and cooling needs.
Recommended combination | 2 x FXSQ32A2VEB + 2 x FXSQ40A2VEB | ||||||
Dimensions | Unit | Width | 900 | mm | |||
Depth | 320 | mm | |||||
Height | 1,345 | mm | |||||
COP at nom. assets | 6°C N.B | 3.90 | kW/kW | ||||
Capacity range | 6 | H.P | |||||
Compressor | Type | Hermetically sealed swing compressor | |||||
Sound pressure level | Cooling | Nom. | 51.0 (5) | dBA | |||
Weight | Unit | 104 | kg | ||||
Index connection inside | Max. | 182.0 | |||||
Min. | 70.0 | ||||||
Cooling capacity | Prated, c | 15.5 (1) | kW | ||||
Cooling | A-conditions (35 °C – 27/19) | HONOR | 2.6 | ||||
Pdc | 15.5 | kW | |||||
B conditions (30 °C – 27/19) | HONOR | 4.8 | |||||
Pdc | 11.4 | kW | |||||
C conditions (25 °C – 27/19) | HONOR | 9.1 | |||||
Pdc | 7.3 | kW | |||||
D conditions (20 °C – 27/19) | HONOR | 15.1 | |||||
Pdc | 4.6 | kW | |||||
Coolant | Charge | 3.6 | kg | ||||
GWP | 2,087.5 | ||||||
Type | R-410A | ||||||
Pipe connections | Gas | Outer diameter | 19.1 | mm | |||
Type | Brazing joint | ||||||
Total pipe length | System | Really | 300 (6) | m | |||
Liquid | Outer diameter | 10 | mm | ||||
Type | Flare connection | ||||||
Maximum number of connectable indoor units | 64 (3) | ||||||
Power consumption | 50Hz | To heat | Nom. | 6°CNB | 3.97 (2) | kW | |
SCOP | 4.4 | ||||||
SEER | 6.8 | ||||||
Sound power level | Cooling | Nom. | 70.0 (4) | dBA | |||
Voltage supply | Phase | 3N~ | |||||
Frequency | 50 | Hz | |||||
Name | Y1 | ||||||
Tension | 380-415 | V | |||||
Heating (temperate climate) | A conditions (-7 °C) | COPd (available coefficient of performance) | 2.9 | ||||
Pdh (available heating power) | 9.0 | kW | |||||
B conditions (2 °C) | COPd (available coefficient of performance) | 4.0 | |||||
Pdh (available heating power) | 5.5 | kW | |||||
C conditions (7 °C) | COPd (available coefficient of performance) | 6.5 | |||||
Pdh (available heating power) | 3.6 | kW | |||||
D conditions (12 °C) | COPd (available coefficient of performance) | 8.1 | |||||
Pdh (available heating power) | 4.3 | kW | |||||
TOLL | COPd (available coefficient of performance) | 2.5 | |||||
Pdh (available heating power) | 10.2 | kW | |||||
TOL (operating temperature) | -10 | °C | |||||
Tbivalent | COPd (available coefficient of performance) | 2.5 | |||||
Pdh (available heating power) | 10.2 | kW | |||||
Tbiv (bivalent temperature) | -10 | °C | |||||
Heating capacity | Nom. | 6°CNB | 15.5 (2) | kW | |||
Prated, h | 15.5 (2) | kW | |||||
Operating range | Heating | Max. | 15.5 | °CWB | |||
Min. | -20.0 | °CWB | |||||
Cooling | Max. | 46.0 | °CDB | ||||
Min. | -5.0 | °CDB | |||||
ηs,c | 268.3 | % | |||||
ηs,h | 174.1 | % |