Description
Experience unparalleled comfort and efficiency with the Daikin VRV Air-Cooled Heat Pump. This versatile unit supports a wide range of indoor units, including the sophisticated Daikin Emura and Nexura models, allowing for seamless integration with your existing VRV or stylish indoor setups.
Key Features
- Wide Compatibility: Connect a variety of indoor units, from VRV systems to stylish options like Daikin Emura and Nexura, ensuring a tailored solution for any space.
- Advanced VRV IV Technology: Benefit from Variable Refrigerant Temperature (VRT) and full inverter compressors for superior energy efficiency and optimal performance.
- Peak Consumption Control: Limit peak power consumption between 30% and 80% during high-demand periods, providing flexibility and cost savings.
- Weather-Dependent VRT: Customize your VRV system for optimal seasonal efficiency and comfort with intelligent, weather-responsive variable refrigerant temperature.
- i-NET Monitoring Service: Keep your system running smoothly with continuous monitoring, defect prediction, and clear insights into operating conditions and usage for maximum efficiency and longevity.
- Comprehensive Thermal Solutions: Address all thermal needs from a single point of contact, including precise temperature control, ventilation, air handling, and Biddle air curtains.
- Compact & Lightweight: Designed with a single fan for a discreet, almost invisible installation that fits seamlessly into any environment.
- Night Mode: Enjoy quieter operation at night with a 3-stage night mode, reducing noise levels for a more peaceful environment.
- Inverter Technology: Inverter compressors adjust continuously to actual demand, reducing energy consumption by up to 30% and maintaining more stable temperatures.
- Enhanced Comfort and Savings: The intelligent system ensures maximum energy savings with enhanced comfort to better meet application requirements.
Upgrade to the Daikin VRV Air-Cooled Heat Pump for a cutting-edge, efficient, and versatile heating and cooling solution that meets all your building's thermal needs while offering exceptional comfort and energy savings.
RXYSCQ4TV1 | |||
---|---|---|---|
Capacity Range | Horse | 4 | HP |
Cooling Capacity | Nominal | 12,1 | kW |
Heating Capacity | Nominal Maximum |
12,1 14,2 |
kW kW |
Absorbed Power 50hz |
Cooling Nom. Isıtma Name / Max |
3,43 3,18/4,14 |
kW kW |
COP | Nom./Max. | 3,53/3,81 | kW |
Dimensions | Height Width Depth |
823 940 460 |
mm mm mm |
Weight | 94 | kg | |
Fan-Air Flow Cooling |
Nominal | 91 | m³/dak |
Sound Power Level | Nominal | 68 | dB(A) |
Sound Pressure Level | Nominal | 51 | dB(A) |
Operating Temperature Range | Soğ. Min~Max Isıt. Min~Max |
-5~46 -20~15,5 |
° C KT ° C KT |
Pipe Connections | Liquid Gas |
9,52 15,9 |
mm mm |
Current-50Hz | Sigorta Amperi | 32 | A |
Signal Cable Cross Section | 2 x 1 | mm | |
Energy Cable Section | 3 x 6 | mm | |
Minimum Circuit Amps | MCA | 29,1 | A |
Power Supply | Phase/Freq./Voltage | 1~/50/220-240 | Hz / V |